THE
TOTALIZE MODE
The totalize mode
registers a precise total count. Use the totalize mode for cumulative
totals and stopwatch (timer) applications. Meter up-counts (positive scale
factor) or down-counts (negative scale factor).
To use the meter as a totalizer permanently, set the function to totAL
and store the change in nonvolatile memory (to retain the change if power
loss occurs). The meter defaults to the up-count mode. To count down,
use a negative scale factor and a positive offset (display = input x scale
+ offset).
In case of power failure, if the S1-10 switch is set to open the meter
blanks the display and stores the latest reading in nonvolatile memory.
TOTALIZER
EXAMPLE
You are totalizing pulses from a flowmeter which generates 25 pulses
per gallon. To show the total value in gallons:
* Set the meter to the totalize mode.
* Use divide (IN /SC) by 25 as a scale factor
* Store set up information in nonvolatile memory.
Refer to Table 6-1 for summary list of menu configurations.
Follow these steps for the above example:
1. Press the MENU button. The meter shows "Func".
2. Press the
SET button until the meter flashes "totAL".
3. Press the MENU button. The meter shows "SCALE".
4. Press the
SET button. The meter shows "IN .SC" or "IN/SC", with the multiply
(.) or divide by (/) symbol flashing. Press the
SET button until the meter shows "IN/SC".
NOTE: Use multiply (.) when scale factor is less than 1, use divide
by (/) when scale factor (or pulses/units) are greater than 1.
5. Press the
ADV button. The meter shows actual scale value, with left-most
digit flashing.
6. Press the
SET button to enter 25.0000 as the digit's value. Press the
ADV button to scroll horizontally through the display. Press the
SET button
to change the flashing digit's value or flashing decimal point position.
7. Once the meter shows "25.0000", press the MENU button
to store the value. The meter shows "OFFSEt". In most up-count applications
"OFFSEt = 0", which means the meter will RESET to 0.
8. Press the MENU button again to show "dEC Pt". This is
the measurement decimal point, not the scale value decimal point.
9. Press the
SET button to show either "AUto" or currently set decimal point
(decimal point flashes). Press the
ADV button (if required) to change from "Auto" to "F.FFFFF".
10. Press the
SET button until the meter shows "FFFFFF" to read in whole gallons
or "FFFFF.F" to read in tenths of a gallon.
11. Press the MENU button to save this decimal point to
volatile memory. The meter will show "CONfIG".
12. Press the MENU button until the meter shows "noStor".
13. Press the
SET button. The meter shows "StorE".
14. Press the MENU button. If signal were connected to the
input, the meter would begin counting input pulses.
NOTE: Press the RESET button at any time to cause the meter
to start counting with the latest changes in effect, but these changes
will not automatically be stored in the nonvolatile memory.
STOPWATCH IN THE TOTALIZE
MODE
To use the stopwatch (timer) in the totalize mode, close S1-4 and S1-9
jumpers to connect 120/100 Hz (twice the line frequency) to the input.
Use the following scale factors:
* For readings in seconds, divide by 120 (or 100)
* For readings in minutes and fractions of a minute, divide by
7,200 (or 6,000)
* For readings in hours and fractions of an hour, divide by 432,000
(or 360,000) (for example: 12.65 hours)
Use external gate input (TB2-5) to stop and start the timer. The meter
increments when the Ext. Gate input is high, or open. A contact closure
between pins TB2-5 and TB2-3 will stop the timer.
DOWN COUNTING
To count down: Use a negative scale factor (reading = input x scale
+ offset) and a positive offset (if an offset is required). Press the
RESET button to cause the counter to begin counting down from the
offset. After reaching zero, the counter continues to count down negative
numbers.
|